ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
13/05/15
|
Version 2.0
Page 123
Ground source heat pump
1. Proceed in reverse order.
2. Charge the refrigerant circuit refer to
"Refrigerant Handling" on page 86
2.2.14. Replacing the water expansion vessel
2.2.14.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Open the sound insulation of the heat pump module (front side), refer to
"Opening the sound insulation of the heat pump
module (front side only)" on page 89
3. Drain the water circuit, refer to
"Draining the water circuit" on page 87
.
2.2.14.2 Procedure
Removal
1. Loosen but do not remove the 2 screws (
) that fix the water expansion vessel upper support
.
2. Lift the water expansion vessel
and tilt it to the left.
3. Remove the water expansion vessel
from the water expansion vessel lower support
and put it aside.
4. Loosen the nut
that fixes the flexible hose.
5. Remove the water expansion vessel
.
6. Remove the seal
Figure 42 - Replacing the water expansion vessel
Installation
1. Screw
4. Water expansion vessel lower support
2. Water expansion vessel upper support
5. Nut
3. Water expansion vessel
6. Seal
C
AUTION
If damaged, replace the seal (6).
C
AUTION
If required, adjust the pressure of the water expansion vessel.
3
2
5
1
4
6