ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
13/05/15
|
Version 2.0
Page 139
Ground source heat pump
Figure 58 - Replacing the refrigerant high pressure sensor - 2
5. From the front side, release the 3 velcro strips
on the compressor insulation
and open the compressor insulation
.
Figure 59 - Replacing the refrigerant high pressure sensor - 3
6. From the rear side, remove the compressor insulation.
7. Use a welding blanket (1) to protect the components that surround the refrigerant high pressure sensor (2).
8. Place 2 wet cooling clamps (3) on the refrigerant high pressure sensor (2) body.
9. Braze the refrigerant high pressure sensor piping.
1. Screw
4. Velcro strip
2. Bracket
5. Velcro strip (compressor)
3. Sound insulation
1. Velcro strip
3. Compressor
2. Compressor insulation
4
1
1
3
3
2
3
1
1
4
4
4
5
1
1
1
2
3
Содержание EGSQH10S18AA9W
Страница 1: ...Service Manual Ground source heat pump EGSQH10S18AA9W ESIE13 03 Version 2 0 ...
Страница 82: ...ESIE13 03 Part 2 Troubleshooting 4 Component checklist Page 82 13 05 15 Version 2 0 Ground source heat pump ...
Страница 148: ...ESIE13 03 Part 3 Repair 2 Unit specific repair procedures Page 148 13 05 15 Version 2 0 Ground source heat pump ...