ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 98
13/05/15
|
Version 2.0
Ground source heat pump
Figure 17 - Replacing the A10P PCB
Installation
1. Proceed in reverse order.
2.2.3. Cleaning the brine filter
2.2.3.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the front panel, refer to
"Removing the front panel" on page 85
.
3. Remove the top panel, refer to
"Removing the top panel" on page 88
4. Partially drain the brine circuit, refer to
"Draining the brine circuit" on page 86
.
1. A10P PCB
4. Frame
2. Screw
5. Heat sink
3. Hex coupling nut
6. Tie wrap
W
ARNING
All hazardous waste shall be managed in accordance with federal, state and local regulations.
1
2
4
5
6
3