ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 104
13/05/15
|
Version 2.0
Ground source heat pump
2.2.6. Replacing the water flow sensor
2.2.6.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the front panel, refer to
"Removing the front panel" on page 85
.
3. Partially drain the water circuit, refer to
"Draining the water circuit" on page 87
.
2.2.6.2 Procedure
Removal
1. Loosen the water flow sensor connector nut (2).
2. Unplug the water flow sensor connector (3).
3. Loosen the 2 nuts (4) that fix the water flow sensor (1).
4. Remove the water flow sensor (1).
5. Wipe off any spilled water.
Figure 23 - Replacing the water flow sensor
Installation
1. Proceed in reverse order.
2. Fill the water circuit, refer to “To fill the space heating circuit” in the Daikin Altherma ground source heat pump Installer
reference guide.
3. Purge the water circuit, refer to “9.3 Air purge function on the space heating circuit” in the Daikin Altherma ground source heat
pump Installer reference guide.
1. Water flow sensor
4. Nut
2. Water flow sensor connector nut
5. Arrow (flow direction)
3. Water flow sensor connector
I
NFORMATION
The arrow
(5)
indicating the water flow direction must point to the LEFT.
4
4
4
5 1
4
3
2