ESIE13-03
|
Part 2. Troubleshooting
4. Component checklist
13/05/15
|
Version 2.0
Page 71
Ground source heat pump
6. Power the Daikin Altherma GSHP.
7. Measure the voltage across connector X17A: pin 1-3; compare the measured voltage with the expected voltage.
8. In case no voltage is measured across connector X17A: pin 1-3; do following checks:
9. Is PCB A09P powered?, if not check power supply.
10. Is connector X17A plugged in PCB A09P?, if not plug in X17A.
11. Is 5 VDC measured across connector X17A: pin 3-4?, if not replace PCB A09P.
-
In case all 3 checks above are OK but still no voltage is measured between X17: pin 1-3, replace the high pressure sensor
B1PH, refer to
"Replacing the refrigerant high pressure sensor" on page 137
.
4.12. High pressure switch S1PH
I
NFORMATION
The high pressure sensor connector must be plugged into X17A on PCB A09P.
Technical specification
Description
The high pressure switch S1PH has a normally closed contact. If the pressure
exceeds 41.7 (+0 / - 1) bar the contact will open; if the pressure drops below
32 (±2) bar the contact will close.
The high pressure switch S1PH is a safety com-
ponent that stops the compressor if overpressure
is detected in the refrigerant circuit.
Location
Piping diagram
Switch box
Unit
Check procedure
+5V
Red
X17A
GND
Black
White
High pressure sensor
Microcomputer
A/D input
Measure DC voltage here
Outdoor unit PC board A09P
1
2
3
4