ESIE13-03
|
Part 2. Troubleshooting
3. Symptom based troubleshooting
13/05/15
|
Version 2.0
Page 43
Ground source heat pump
Out of operation range
(ambient temperature
above 35°C).
Ambient temperature
higher than 35°C.
No action - unit cannot operate when
ambient temperature is above 35°C.
Activation of the brine
freeze up protection con-
trol.
Several conditions possi-
ble to have brine freeze up
protection control active (in
function of Tf (setting
[A-04])):
1. Brine out temp (R6T
out) < Tf + 3,5 K
2. Brine in temp (R5T out)
< Tf + 6,5 K
3. Te* < Tf - 3,5 K
4. Te* < Tf - 2,5 K for
30 seconds
5. Te* < Tf - 1,5 K for
2 minutes
Te*: lowest value meas-
ured comparing following
sensor (R4Tout, R3Tout,
R6Tout).
Check brine in temperature (possible via
installer level of the user interface) and
compare with the freeze up temperature
Tf (setting [A-04]).
If required change brine
mixture and program
freeze up temperature
accordingly.
Root cause category: end user
Space heating or domes-
tic hot water operation is
not activated on the user
interface.
Confirm if space heating operation or
domestic hot water operation is activated
on user interface.
Activate space heating or
domestic hot water opera-
tion on the user interface.
Root cause category: parameter (setting)
Displayed date/time is
wrong - schedules not cor-
rectly executed.
• Not set date/time after
initial startup.
• No power supply for
more than 48 hours.
Set date/time according to operation man-
ual instructions.
Set date/time according to
operation manual instruc-
tions.
Displayed date/time is
wrong - schedules not cor-
rectly executed.
Daylight Saving Time not
set correctly.
Check Daylight Saving Time settings.
Set Daylight Saving Time
according to operation
manual.
Incorrect setting of unit
control method (setting
[C-07]).
Incorrect setting of unit
control method (setting
[C-07]) (leaving water con-
trol, room thermostat con-
trol, ext. room thermostat
control).
Check if setting [C-07] (leaving water con-
trol, room thermostat control, ext. room
thermostat control) is in set according to
the application.
Incorrect setting of user
interface location (user
menu [A.2.1.B]).
Incorrect setting of user
interface location (user
menu [A.2.1.B]) (at unit/in
room).
Check if setting of user interface location
(user menu [A.2.1.B]) (at unit/in room) is
set correctly.
Incorrect setting of space
heating OFF temperature
(setting [4-02]).
Incorrect setting of space
heating OFF temperature
(setting [4-02]).
Check if setting space heating OFF tem-
perature (setting [4-02]) is correct (keep at
35°C).
Preferential kWh rate
power supply settings and
electrical connections do
not match.
Preferential kWh rate
power supply settings and
electrical connections do
not match.
Check preferential kWh rate power supply
settings and electrical connections.
Root cause category: component - electrical
Deviation of brine entering
(R5T - A9P) thermistor can
cause incorrect activation
of brine freeze up temper-
ature.
• Component
problem.
• Bad contact between
sensor and piping.
Check thermistor R5T - A9P (see
Replace thermistor R5T
(see
) or PCB
Possible failures
Root cause
Check
Corrective action