ESIE13-03
|
Part 2. Troubleshooting
2. Error code based troubleshooting
13/05/15
|
Version 2.0
Page 31
Ground source heat pump
2.33. “P1” – Open phase or power supply voltage imbalance
2.34. “P4” – Inverter radiation fin thermistor (R10T) error
2.35. “PJ” – Defective capacity setting
2.36. “UA” – PCB combination error
Trigger
Effect
Reset
Inverter PCB detects incorrect power sup-
ply.
Unit will stop operating.
Auto-return.
Possible cause
Check
Corrective action
Power supply is not OK -> open phase.
Check the power supply.
Power supply is not OK -> imbalance
> 10% (rated power supply: 400 V).
Check power supply for voltage fluctua-
tions (> 10%).
Voltage fluctuations should be less than
10%.
Faulty inverter PCB A10P.
Check inverter PCB (see
).
Replace inverter PCB (see
).
Missing phase for 3 phase unit.
Check the power supply.
Correct power supply.
Trigger
Effect
Reset
Thermistor R10T detects an abnormal
value (open or short circuit).
Unit will stop operating.
Auto-reset when problem is solved.
Possible cause
Check
Corrective action
Faulty inverter heat sink thermistor R10T /
inverter PCB A10P.
Check thermistor R10T (see
)
Check inverter PCB (see
).
Replace thermistor R10T (see
)
or PCB A10P (see
).
Faulty inverter PCB A10P.
Check inverter PCB (see
).
Replace inverter PCB (see
).
Faulty refrigerant/brine PCB A9P.
Check refrigerant/brine main PCB A9P.
Replace refrigerant/brine main PCB A9P
(see
Trigger
Effect
Reset
Refrigerant/brine PCB detects a defective
capacity in EEPROM.
Unit will stop operating.
Via user interface.
Possible cause
Check
Corrective action
Positions of PCB dipswitches are not OK.
Check if dipswitches are set to default
(OFF) position.
Faulty refrigerant/brine PCB A9P.
Check if the alive led is blinking in regular
intervals.
If not blinking in regular intervals, replace
the PCB A9P.
Trigger
Effect
Reset
System detects combination mismatch
between refrigerant/brine main PCB A9P
and hydro PCB A1P or inverter PCB
A10P.
Unit will stop operating.
Auto-reset.
Possible cause
Check
Corrective action
Wrong unit combination.
Check combination database.
Correct installationì.
Wrong field setting for compressor type.
Check setting [E-01].
Set setting [E-01] to correct value.