ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 130
13/05/15
|
Version 2.0
Ground source heat pump
3. Through the opening in the rear of the switch box, move the manometer capillary (3) towards the top of the Daikin Altherma
GSHP, while pressing the insulation where the manometer capillary (3) is attached with a tie wrap (4) to allow the nut (2) to
pass.
4. Guide the manometer capillary (3) through the opening in the water manometer support (6).
Figure 50 - Replacing the water manometer - 1
1. Water manometer
5. Switch box opening
2. Nut (water manometer capillary)
6. Water manometer support
3. Manometer capillary
7. Insulation
4. Tie wrap
C
AUTION
The water manometer capillary is wrapped
with insulation
at the gauge. Keep the insulation to insulate the new
water manometer.
3
4
4
5
2
6
1
7