ESIE13-03
|
Part 2. Troubleshooting
3. Symptom based troubleshooting
13/05/15
|
Version 2.0
Page 45
Ground source heat pump
3.6. Water leakage or water release via the water pressure relieve valve
Root cause category: component - electrical
Leaving water thermistor
(R1Tin - A1P) deviation
causes incorrect temperature
control.
• Deviation
of
thermistor
(lower temperature
measured than actual).
• Bad
contact
between
sensor and pipe.
Check thermistor R1Tin (see
).
Replace R1T or PCB A1P (see
).
Deviation of domestic hot
water tank thermistor (R5Tin -
A1P). (Remark: only valid for
inaccurate domestic hot water
temperature control.)
• Deviation
of
thermistor.
• Bad
contact
between
sensor and pipe.
Check thermistor R5Tin (see
).
Replace thermistor R5T (see
).
User interface (A2P) - thermo-
stat sensor has incorrect read-
ing of room temperature.
Deviation of user interface
room temperature sensor.
Compare temperature meas-
ured by user interface with
actual room temperature.
In case of deviation the room
temperature offset can be
adjusted through setting
[2-0A].
Possible failures
Root cause
Check
Corrective action
Root cause category: installation
Drain connection of water
safety valve (SV2) leaking.
Bad connection between unit
drain pipe and field drain pipe.
Check the drain connection of
the water safety valve.
Correct the drain connection if
required.
Drain of bottom drain plate not
well connected.
Bad connection of bottom
drain plate and field drain con-
nection
Check the drain connection
between the bottom drain
plate and the field drain
Correct the drain connection if
required.
Leakage of drain valve water
side (DR3, DR4).
Valve not completely closed.
Check if drain valve is closed.
Close the drain valve.
Root cause category: component - mechanical
Broken bellow of brine side
expansion vessel (EXP1).
Component failure.
Check expansion vessel (see
).
Replace expansion vessel
(see
Expansion vessel (EXP1) not
pressurized.
Component failure.
Check expansion vessel (see
).
Replace expansion vessel
(see
Safety valve water side (SV2)
blocked.
Component failure.
Check safety valve (see
).
Replace safety valve (see
Safety valve water side (SV2)
leaking.
Component failure.
Check safety valve (see
).
Replace safety valve (see
Leakage of drain valve water
side (DR3, DR4).
Component failure.
Check drain valve.
Replace drain valve.
Domestic hot water tank leak-
age.
Component failure.
Check tank visually for leak-
ages.
Repair leakages. If not possi-
ble, complete unit has to be
replaced.
Air Purge (AP) leakage.
Component failure.
Check air purge valve for leak-
ages.
Replace air purge valve.
Possible failures
Root cause
Check
Corrective action