Page 129
Ground source heat pump
Figure 49 - Replacing the 3-way valve body
Installation
1. Proceed in reverse order.
2. Fill the water circuit, refer to “To fill the space heating circuit” in the Daikin Altherma ground source heat pump Installer
reference guide.
3. Purge the water circuit, refer to “9.3 Air purge function on the space heating circuit” in the Daikin Altherma ground source heat
pump Installer reference guide.
2.2.18. Replacing the water manometer
2.2.18.1 Preliminary actions
1. Remove the front panel, refer to
"Removing the front panel" on page 85
2. Remove the top panel, refer to
"Removing the top panel" on page 88
.
3. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
.
4. Drain the water circuit, refer to
"Draining the water circuit" on page 87
.
5. Remove PCB A10P, refer to
"Procedure: replacing the A10P PCB" on page 97
.
2.2.18.2 Procedure
Removal
1. Loosen the nut (2) and remove the manometer capillary (3) from the water pressure relief valve.
2. Press the water manometer (1) out of the water manometer support (6).
1. 3-way valve body
2. Clip
C
AUTION
When installing the 3-way valve motor on the 3-way valve, refer to Installation of
"Replacing the 3-way valve motor" on
C
AUTION
The capillary connection is sealed by a copper seal; when removing the water manometer capillary from the pressure
relieve valve, make sure not to lose the copper seal.
C
AUTION
The capillary (3) is held in position by 2 tie wraps (4). Press the insulation at the position of the tie wraps (4) to release
the capillary; the same tie wraps (4) will be used when installing the new water manometer (1).