ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
13/05/15
|
Version 2.0
Page 115
Ground source heat pump
Figure 32 - Replacing the brine pressure relief valve - 1
Installation
1. Proceed in reverse order.
2. Fill the brine circuit, refer to “To fill the brine circuit” in the Daikin Altherma ground source heat pump Installer reference guide.
2.2.12. Replacing the water pump
2.2.12.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the front panel, refer to
"Removing the front panel" on page 85
3. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
.
4. Unlock the power input section, refer to
"Unlocking the pivoting power input section" on page 90
.
5. Drain the water circuit, refer to
"Draining the water circuit" on page 87
.
1. Coupling
4. Glue remainder
2. Nut
5. Seals
3. Pressure relief valve
C
AUTION
If damaged, replace the seals (5).
I
NFORMATION
When gluing the water pressure relief valve (3) to the coupling (1), make sure it is in the same angle as in figure 31 on
page 114.
5
5
5
1
2
4