ESIE13-03
|
Part 2. Troubleshooting
3. Symptom based troubleshooting
13/05/15
|
Version 2.0
Page 53
Ground source heat pump
3.15. User interface (no or strange display)
Possible failures
Root cause
Check
Corrective action
Root cause category: component - electrical
Hydro PCB A1P not opera-
tional
• No power supply
• Faulty
transformer
TR1
• PCB
malfunction
•
Confirm if a small green led
is blinking in regular
intervals
• Confirm power supply
towards PCB A1P
• Check good operation of
transformer TR1
• Re-establish power to PCB
• Replace PCB A1P (see
) in case power
supply and transformer
TR1 are OK but led is not
blinking
Reactor coil (L1R/L2R/L3R)
broken
Component problem
Check continuity of the reactor
coil
Replace the reactor coil in
case faulty
P1P2 transmission cable bro-
ken/short-circuit
Check P1P2 cable (16 VDC
on BRC terminals and cable
continuity)
Repair P1/P2 cable if required
User interface (A2P) failure
Replace user interface