109
CTC EcoZenith i360
HP Noise reduction
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
This function can be used to reduce compressor speed
in order to reduce the noise level.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer / Define/Heat Pump" menu:
• configure the normal mode for the external control
signal (Normally Open (NO)/Normally Closed (NC))
in the "Noise reduction ext. config." row.
In the "Installer/Settings/Heat Pump" menu:
• in the "Ext. Noise reduction rps" row, set the
compressor speed value applicable for remote
control.
For more information, refer to the "Heating Pump"
section in the "Installer/Settings" chapter.
HP Night Mode
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
This function can be used to reduce compressor speed
and fan speed in order to reduce the noise level.
Only applies to air-to-water heat pumps.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer / Define/Heat Pump" menu:
• configure the normal mode for the external control
signal (Normally Open (NO)/Normally Closed (NC))
in the "Silent mode ext. config." row.
For more information, refer to the "Heating Pump"
section in the "Installer/Settings" chapter.
Menu: "Installer/Define/Heat Pump".
A mode for the external control signal ("Normally Open (NO)"
or "Normally Closed (NC)") is defined for "Noise reduction ext.
config.".
Menu: "Installer/Settings/Heat Pump".
Set the compressor speed value applicable for remote control
in the "Ext. Noise reduction rps" row.
Содержание EcoZenith i350 L 1x230V
Страница 3: ...162 505 77 1 2020 09 15 Installation and Maintenance Manual CTC EcoZenith i360 ...
Страница 127: ...127 CTC EcoZenith i360 ...
Страница 128: ......
Страница 129: ......
Страница 130: ......
Страница 131: ......
Страница 132: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 77 1 2020 09 15 ...