background image

Quick Reference Installation Guide

For gas delivery to the boiler, we recommend using 

hard piping rather than flexible piping. If you use 

flexible piping, ensure that the gas pipe size is 

appropriate for the maximum BTU input of the boiler.

Minimum Gas Pressure

4" w.c.

Maximum Gas Pressure

14" w.c.

 

Size piping for sufficient sustained gas delivery at 

sufficient pressure to the boiler.

Recommended Supply Pressure at Full Load

Natural Gas

7"

Propane

10"

• 

Ensure that there is a minimum of 6 feet of piping 

between the boiler and gas regulators. 

• 

Use a manometer to test that gas delivered to the 

boiler is delivered at sufficient pressure and that 

“lock up” does not exceed the maximum pressure.

• 

If using a 5 psi to inches vented gas regulator, 

always oversize the vent pipe to prevent hunting 

of the gas regulator when boilers are firing at 

lower output levels.

•  We strongly recommend against using copper gas 

lines. In retrofits with existing copper gas pipes, 

we highly recommend replacing the pipes with 

black iron or stainless steel piping sized correctly 

for the boiler. If the copper gas pipes must remain, 

clean and clear the gas piping of any debris before 

connecting to the boiler. Failure to do so can 

result in a blocked gas valve. and inconsistent 

performance. 

 

Maximum Pipe 
Length by Model

½" 
IPS

¾" 
IPS

1" 
IPS

1¼" 
IPS

CX 150 (Natural Gas)

20’

80’

200'

900’

CX 150 (Propane)

50

'

200'

600

'

2,000’

CX 199 

(Natural Gas)

10'

40'

150'

900'

CX 199 

(Propane)

30'

125'

400'

1,400'

1. 

Place the vacuum breaker cap over the 

vacuum breaker opening and push firmly

2.  Fill the condensate trap with water.
3. 

Attach the trap to the drain hose, and tighten 

the drain compression (including washer)

4. 

Slide the trap over the boiler drain outlet, and 

tighten upper union nut. Secure the upper 

union nut with the outlet clip.

5.  Check for leaks.

Gas Supply 

(

Section 

3.12

)

Boiler Mounting 

(Manual 

Section 3.4

)

Venting 

(Sections 3.5 and 3.7)

 

• 

Ensure that sidewall configurations have a minimum 

12" vertical separation, and that exhaust plumes are 

well away from all building air intake vents.

•  Ensure that all venting material is sloped towards 

the boiler. PP venting must be sloped at a minimum 

of ⅝″ per foot to ensure that no leaks occur via 

gaskets.

• 

Ensure that PP venting is supported every 36″ (min).

• 

On longer horizontal runs of PVC and CPVC, 

increase the grade to ⅜″ or more.

•  Fully insert approved venting material into the 

boiler’s exhaust outlet. Then, tighten the clamp 

to lock the venting in place. For PP venting, a 

transition adapter is not required.

•  Pull on the venting to check it’s securely attached to 

the boiler exhaust outlet.

Important:

 To protect against wind loads, 

terminate exhaust venting as shown, or use the 

appropriate direct vent kit.

Condensate Trap 

(

Section 

3.9

)

LWCO Errors 

To clear LWCO errors caused by air:
1. 

Ensure that there is no air trapped in the 

boiler and boiler piping.

2. 

On the touchscreen controller 

Status

 Menu, 

go to 

Clear Errors 

Yes

1. 

Ensure that the boiler’s mounting bracket is 

securely bolted to the wall structure.

2.  Fasten the bottom of the boiler to the wall.

Important:

 Not applicable for construction 

heating. Parts such as fans, burners, and 

ignitors fouled by construction are not covered 

under warranty.

120-414E1 CX Quick Start

 

Отзывы: