89
CTC EcoZenith i360
Cold temp limit
0 (0...-15)
When the outdoor temperature is equal or lower (T2),
the compressor speed is adjusted up to speed R2.
Only applies to modulating air-to-water heat pumps.
Warm temp limit
20 (0...20)
When the outdoor temperature is equal or higher (T1),
the compressor speed is adjusted down to speed R1.
The heat pump starts and stops at the actual value and
setpoint value.
Only applies to modulating air-to-water heat pumps.
Passive cooling brine pump on
On (On/Off)
Enable "Yes" if the brine pump should be used for
passive cooling.
Only applies to liquid-to-water heat pumps.
Silent mode, schedule
It is possible to start a weekly program, e.g. during the
night, with limited compressor speed and fan speed to
reduce the noise level.
The "Weekly Program" chapter describes how to set
schedules.
Only applies to CTC EcoAir 600M.