AC Repair and Adjustment Procedures
FRP 40: Transformer (T1) Replacement
HMM-168-A
Cray Research/Silicon Graphics Proprietary
191
FRP 40: Transformer (T1) Replacement
Part Number
The blower control transformer is purchased as a unit with the blower controller
(SCR1) and has the same part number. You must order the transformer with
SCR1.
•
57067701 (controller, power SCR 20A with transformer)
Tools Required
•
#2 Phillips screwdriver
•
#1 Phillips screwdriver
Transformer Removal
1.
Open the cabinet’s front door.
2.
Open the cabinet’s main disconnect circuit breaker (CB1) and unplug the
cabinet. Place a lockout device over the cabinet’s plug and lock/tag it.
You may also open, lock, and tag the customer’s wall breaker(s).
3.
Open the blower circuit breaker (CB8).
WARNING
Ensure that the electrical plug for the
equipment that you service is
unplugged, locked, and tagged. Failure
to do so could result in severe shock
and burns.