FRP 28: Blower Control Fuse Replacement
AC Repair and Adjustment Procedures
150
Cray Research/Silicon Graphics Proprietary
HMM-168-A
FRP 28: Blower Control Fuse Replacement
Each cabinet contains two 0.2-A fuses, which protect the transformer that
provides 24-Vac power to the blower controller (SCR1).
locations of the fuses.
Part Number
•
57084701 (fuse, 250V 2/10 amp)
Tools Required
•
Small flatblade screwdriver
•
Multimeter (ohmmeter)
Fuse Replacement
1.
Open the front cabinet door.
2.
Open the cabinet’s main disconnect circuit breaker (CB1) and unplug the
cabinet. Place a lockout device over the cabinet’s plug and lock/tag it.
You may also open, lock, and tag the customer’s wall breaker(s).
3.
Open the blower circuit breaker (CB8).
4.
Open the WACS panel.
5.
Remove the fuses, one at a time, and check for continuity with an
ohmmeter. (Use a flatblade screwdriver to remove the fuse cover.)
WARNING
Ensure that the electrical plug for the
equipment that you service is
unplugged, locked, and tagged. Failure
to do so could result in severe shock
and burns.