AC Repair and Adjustment Procedures
FRP 28: Blower Control Fuse Replacement
HMM-168-A
Cray Research/Silicon Graphics Proprietary
151
6.
Install the replacement fuse(s). (Ensure that replacement fuses meet the
required specifications.)
7.
Close the WACS panel.
8.
Plug in the cabinet, close the main disconnect circuit breaker (CB1), the
blower circuit breaker (CB8), and the WACS circuit breaker (CB9), and
check blower function.
9.
Restore the cabinet to operation, and close the front cabinet door.
10. Periodically, check the cabinet and module temperatures to ensure proper
blower speed control.
Figure 70. Blower Control Fuse Locations
Fuses