Chapter 1 Alarm Troubleshooting
1.7.200 SD-P
Clear the SD-L Condition
Step 1
Complete the
“Clear an OC-N Port Facility or Terminal Loopback Circuit” procedure on page 1-157
.
Step 2
Ensure that the fiber connector for the port is completely plugged in. For more information about fiber
connections, refer to the “Install Hardware” chapter in the
Cisco ONS 15310-CL and
Cisco ONS 15310-MA Procedure Guide
.
Step 3
If the BER threshold is correct and at the expected level, use an optical test set to measure the power
level of the line to ensure it is within guidelines. For specific procedures to use the test set equipment,
consult the manufacturer.
Step 4
If the optical power level is good, verify that optical receive levels are within the acceptable range. The
correct specifications are listed in the “Install Hardware” chapter in the
Cisco ONS 15310-CL and
Cisco ONS 15310-MA Procedure Guide
.
Step 5
If receive levels are good, clean the fibers at both ends according to site practice. If no site practice exists,
complete the procedure in the “Maintain the Node” chapter in the
Cisco ONS 15310-CL and
Cisco ONS 15310-MA Procedure Guide
.
Caution
Always use the supplied electrostatic discharge wristband when working with a powered ONS 15310-CL
or ONS 15310-MA.
Step 6
If the condition does not clear, verify that single-mode fiber is used.
Step 7
If the fiber is of the correct type, verify that a single-mode laser is used at the far-end node.
Step 8
Clean the fiber connectors at both ends for a signal degrade according to site practice.
Step 9
If the problem does not clear, the transmitter at the other end of the optical line could be failing and
require replacement.
Step 10
If the condition does not clear, log into the Technical Support Website at
http://www.cisco.com/techsupport for more information or call Cisco TAC (1 800 553-2447).
1.7.200 SD-P
Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)
SONET Logical Objects: STSMON, STSTRM
An SD Path condition applies to the path (STS) layer of the SONET overhead. A path or ST-level SD
alarm travels on the B3 byte of the SONET overhead.
For path protection-protected circuits, the BER threshold is user-provisionable and has a range for SD
from 1E–9 dBm to 1E–5 dBm. For 1+1 and unprotected circuits, the BER threshold value is not
user-provisionable and the error rate is hard-coded to 1E–6 dBm. An SD-P condition causes a switch
from the working port to the protect port at the path (STS) level.
The BER increase that causes the condition is sometimes caused by a physical fiber problem such as a
poor fiber connection, a bend in the fiber that exceeds the permitted bend radius, or a bad fiber splice.
SD causes the port to switch from working to protect. The SD condition clears when the BER level falls
to one-tenth of the threshold level that triggered it.