A-31
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-23069-07
Appendix A Technical Specifications
Chassis Clearances
Figure A-19
Clearances Required for a Center-Mounted Cisco Nexus 7009 Chassis in a Two-Post
Rack
12
13
14
15
16
10
11
9
304037
8
7
6
5
3
3
17.3 in
(43.9 cm)
12.5 in
(31.
8
cm)
1
8
.0 in
(45.7 cm)
26.0 in
(66.0 cm)
2
8
.0 in
(71.1 cm)
5.0 in
(12.7 cm)
1
2
4
4
1
Cisco Nexus 7009 chassis
9
Right side clearance (for rack installations)
recommended to input air from the cold aisle:
•
If next to another open rack, use 6 inches
(15.2 cm).
•
If next to a wall, use 11 inches (27.9 cm).
2
Cable management frames
10
Chassis width
3
Vertical rack-mount posts
11
Right side clearance (for rack installations)
recommended to input air from the cold aisle:
•
If next to another open rack, use 6 inches
(15.2 cm).
If next to a wall, use 11 inches (27.9 cm).
4
Vertical rack-mount post for neighboring rack
12
Rear service clearance required to replace fan
trays and fabric modules
5
Air intake from cold aisle for power supplies
13
Airflow clearance required between the
chassis and inside of cabinet (if used)
Содержание Nexus 7004
Страница 12: ...Contents xii Cisco Nexus 7000 Series Hardware Installation and Reference Guide OL 23069 07 ...
Страница 19: ... xix Cisco Nexus 7000 Series Hardware Installation and Reference Guide OL 23069 07 ...
Страница 22: ... xxii Cisco Nexus 7000 Series Hardware Installation and Reference Guide OL 23069 07 ...
Страница 24: ...xxiv Cisco Nexus 7000 Series Hardware Installation and Reference Guide OL 23069 7 New and Changed Information ...