A-24
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-23069-07
Appendix A Technical Specifications
Chassis Clearances
Figure A-15
Clearances Required for the Cisco Nexus 7004 in a Two-Post Rack with Front-Mount
Brackets
17.3 in
(43.9 cm)
24.0 in
(61.0 cm)
7.5 in
(19.1 cm)
26.0 in
(66.0 cm)
1
7
9
10
11
12
13
14
6
5
8
2
3
3
3041
8
0
4
4
1
Cisco Nexus 7004 chassis
8
No left side clearance required (no airflow on
left side)
2
Cable management frames
9
Chassis width.
3
Vertical rack-mount posts
10
Right side clearance recommended for open
rack installations:
•
If next to another open rack, use 6 inches
(15.2 cm) between racks.
•
If next to a wall, use 11 inches (27.9 cm)
between the chassis and the wall.
4
Vertical rack-mount posts for neighboring
racks
11
No rear clearance required but the rear must
be open to the hot aisle to exhaust air
Содержание Nexus 7004