SECTION 11 (-FL) FLOWSENSE
®
making
since 1986
water work
Above:
This section allows you to enter the
fluctuation range for the high end of your normal
operating flow. Use the (-) and (+) entries to set the
range.
Note:
You will want to set this allowable range up a
little wider due to the amount of water flow.
Example:
If you set the above limit at 100 gallons per minute.
Then set your (-) limit at 15, and your (+) limit at 15.
You will be alerted if the flow at the high end of the
scale fluctuates by more than fifteen gallons per
minute in either direction.
That is less than 85 gpm or more than 115 gpm
4.
Press the
BACK
key to return to the
FLOW METER, MASTER VALVE, &
PUMP screen (Figure 11.5).
3. On – At - a - Time
The On-At-a-Time section of the controller is used to
set up the number of valves that you want to come
on simultaneously within a program, and also within
the system.
Note:
These settings need to be entered at each
controller in the chain.
From the FLOW METER, MASTER VALVE & PUMP
screen (Figure 11.5).
1.
Press the
ON-AT-A-TIME
Menu key.
The STATIONS ON-AT-A-TIME screen is displayed
(Figure 11.11).
PROG A . . . . . . . . . . . . . . 1 1
STATIONS ON-AT-A-TIME
Within Within
Program System
PROG B . . . . . . . . . . . . . . 1 1
PROG C . . . . . . . . . . . . . . 1 1
An "X" means don't use this
On-At-A-Time as a limit
PROG D . . . . . . . . . . . . . . 1 1
PROG E . . . . . . . . . . . . . . 1 1
DRIP 1 . . . . . . . . . . . . . 1 1
DRIP 2 . . . . . . . . . . . . . 1 1
Figure 11.11
2.
Press the blue
ARROW
keys to move
the cursor to the Program and Within
Program setting desired.
Note:
The default setting is set to 1 on all programs
and within system.
3.
Press the
PLUS
or
MINUS
keys for any
number to change the setting.
•
WITHIN PROGRAM:
This section allows
you to choose the amount of valves that you
want to set as a limit to come on at a time
within a program.
•
WITHIN CONTROLLER:
This section
allows you to choose the amount of valves
that you want to set as a limit to come on at
a time within the controller.
Example:
Within Program Within Controller
Program A 1 2
Program B 1 2
This example allows the user to set up one (1) valve
on at a time for Programs A and B. The controller
will allow both Programs to have one (1) valve each
run simultaneously for a total of two (2) on within
controller.
Example:
Within Program Within Controller
Program A 1 1
Program B 3 3
This example allows the user to set up one (1) valve
on at a time for Programs A. The controller will only
allow one valve to operate while program A is
running. Program B is set up to operate 3 valves on
at a time, and will only operate up to three valves
when Program B is running.
4.
Press the
BACK
key to return to the
FLOW METER, MASTER VALVE, &
PUMP screen (Figure 11.5).
THIS CONCLUDES THE FLOWSENSE®
SECTION