SECTION 11 (-FL) FLOWSENSE
®
®
making
since 1986
water work
Copyright Calsense Inc. 1987-2005
All Rights Reserved
(use * Key for special menu)
RTS CTS DTR DSR CD RI
A: L L L L L L
B: L L L L L L
Serial Num: 12345 CC4 Ver: 4.0.11.26
(the normally expected signal levels)
PART & SERIAL NUMBERS
ET2000-40-MSR-RR
576.i s=6 c=6 A=14400 B=14400
Figure 11.3
You will have to perform a Controller Scan:
7.
Press the
BACK
key.
8.
Press the
SCAN RESULTS
Menu key.
The COMMUNICATIONS SCAN RESULTS screen
is displayed (Figure 11.4).
I - -
J - -
K - -
L - -
E - -
F - -
Found 1 of 2 in chain G - -
H - -
CHAIN DOWN A / A ok
B - -
D - -
COMMUNICATIONS SCAN RESULTS (CHAIN DOWN!)
Start scan
C - -
Figure 11.4
9.
Press the
START SCAN
Menu key to
begin the scan.
Note:
The controller will scan each controller in the
chain.
•
B
“
- -
“ symbol indicates that the
controller in the chain was unsuccessful
at communicating (The Master did not
find the “B” controller).
•
B
“
ok
“ symbol indicates that the
controller was found and is currently
communicating with the master
controller (the “A” controller).
Note:
The scan can only be performed at the Master
controller in the
FLOWSENSE
®
chain. Also the
“Number of controllers in chain.” can only be
adjusted at the master controller.
Example:
Number of controllers in chain 5
Controller position in chain communications address
Master controller A !!A
Slave controller B !!B
Slave controller C !!C
Slave controller D !!D
Slave controller E !!E
THIS CONCLUDES MULTIPLE CONTROLLER
COMMUNICATIONS SETUP
B. MULTIPLE CONTROLLER FLOW SETUP
Setting up a
FLOWSENSE
®
chain involves making
adjustment entries to the Master controller and every
controller that a flow meter or master valve is
physically installed on. Make sure you are familiar
with the following subsections of Section 4 FLOW:
•
A. Flow Meter setup.
•
B. Line Fill & Valve close times.
•
C. Master Valve.
•
D.
Pump.
•
H. Alert Actions.
in addition to the following instructions:
1. Mainline Capacity
System capacity is defined by the max flow rate of
water that your system can operate at during
irrigation.
Note:
This setting will have to be adjusted at the
Master Controller (The controller with the letter “A”
as the right most character in its communications
address).
From the FLOW METER, MASTER VALVE & PUMP
screen is displayed.
1.
Press the
MAINLINE CAPACITY
Menu key (Figure 11.5).
Pump On-at-a-Time
Master Valve Mainline Capacity
Alert Actions Flow Checking
FLOW METER, MASTER VALVE & PUMP
& Valve Close Times
Line Fill Flow Meter
Figure 11.5