SECTION 4 FLOW
making
since 1986
water work
flow rate to the expected? YES
From 30 gpm to 100 gpm -10 / +10
ALLOWABLE
FLOW CHECKING
When Irrigating COMPARE the
Above 100 gpm -15 / +15
(-gpm / +gpm)
Below 30 gpm -5 / +5
Figure 4.15
2.
Press the blue
ARROW
keys to
change the Allowable settings
.
The default settings are:
BELOW: -5 / +5
FROM / TO: -10 / +10
ABOVE: -15 / +15
Note:
The above settings are defaulted in the
controller and can be changed by the user.
3.
To change the settings press the
PLUS
or
MINUS
keys for any number
to change the setting.
Below:
This section allows you to enter the fluctuation
range for the low end of your normal operating flow.
Use the (-) and (+) entries to set the range.
Example:
If you set the below limit at 30 gallons per minute.
Then set your (-) limit at 5, and your (+) limit at 5.
You will be alerted if the flow at the low end of the
scale fluctuates by more than five gallons per minute
in either direction.
That is less than 25 gpm or more than 35 gpm
From / to:
This section allows you to set the
fluctuation limits for the full range of flow. In this box
you want to enter the normal operating range of water
flow. Then in the (-) and (+) blocks enter the range of
fluctuation that you deem normal.
Example:
If you set the limit at 30 gpm to 100 gpm.
Then set your (-) limit at 10, and your (+) limit at 10.
You will be alerted if the flow at the middle of the scale
fluctuates by more than ten gallons per minute in
either direction.
That is less than 20 gpm or more than 110 gpm
Above:
This section allows you to enter the fluctuation
range for the high end of your normal operating flow.
Use the (-) and (+) entries to set the range.
Note:
You will want to set this allowable range up a
little wider due to the amount of water flow.
Example:
If you set the above limit at 100 gallons per minute.
Then set your (-) limit at 15, and your (+) limit at 15.
You will be alerted if the flow at the high end of the
scale fluctuates by more than fifteen gallons per
minute in either direction.
That is less than 85 gpm or more than 115 gpm
4.
Press the
BACK
key to return to the
FLOW METER, MASTER VALVE, &
PUMP screen (Figure 4.1).
Note:
Notice that the Alert Actions option has now
been added to this screen (See figure 4.16).
Pump On-at-a-Time
Master Valve Mainline Capacity
Alert Actions Flow Checking
FLOW METER, MASTER VALVE & PUMP
& Valve Close Times
Line Fill Flow Meter
Figure 4.16
THIS CONCLUDES THE FLOW CHECKING
SECTION