manualshive.com logo in svg
background image

Pagina 8 / 48

CS-R Rev. 2 - Operating Instructions

GB

Deep well.

Make  sure  the  motor  remains  at  least  2-3  metres  above  the
well bottom.
The  well  pumping  filters  must  always  be  below  the  position
occupied by the motor, in order to guarantee correct cooling.
Check if the dynamic level of the well varies, either because of
seasonal  water  level  lowering  or  because  the  pump  is  too
powerful for the dynamic characteristics of the well.

Tank.

When installed correctly, the unit has a cooling jacket.
If the unit is installed horizontally, the motor must always be
submersed  in  water  when  not  being  used;  if  it  is  not,  top-up
completely (paragraph 6.2).

6.4 Unpacking

Inspect  the  device  in  order  to  check  any  damages
which may have occurred during transportation.

Package  material,  once  removed,  must  be  discarded/recy-
cled according to local laws of the destination country.

6.5 Assembly of motor on pump

These  instructions  refer  to  the  motor  only.  Please  strictly
observe  the  assembly  instructions  of  the    pump  manufactu-
rer!
Place  motor  and  pump  horizontally  and  level.  Turn  motor
shaft by hand before assembly. It must turn freely after over-
coming  the  adhesive  friction.  Apply  acid-free,  waterproof
grease  to  the  coupling  internal  toothing.  Remove  nuts  from
the studs of the motor. Aling  the pump so that its in line with
the  lead  exit  of  the  motor  and  guide  pump  and  motor
together. Plase spring rings on the studs and  tighten the nuts
crosswise.
Strictly observe the tigthening torques of the unit manufactu-
rer.
Check  radial  and  axial  clearance  of  the  motor  shaft.  There
must  be  no  rigid  connection  since  otherwise  motor  and
pumps will be damaged during commissioning.
Protect coupling spot against contact.

6.6 Electrical connection

Electrical  connection  must  be  carried  out  only  by  a
qualified  electrician  in  accordance  with  local
regulations.

Follow all safety standards.
The unit must be properly earthed (grounded), also with
a nonmetallic delivery pipe.

Make sure the frequency and mains voltage correspond with
the name plate data.
- general disconnecting switch with minimum contact opening

of 3 mm and suitable block when open;

- a  suitable  heat  device  to  protect  the  motor  set  at  a  maxi-

mum consumption current of not more than 5% of the nomi-
nal current given on the motor plate and with an intervention
time of less than 30 seconds;

- a suitable magnetic device for protecting the cables against

short-circuits;

- a  suitable  protective  device  that  sections  the  power  in  the

case of motor pump faults towards earth;

Install electrodes to protect the pump against dry running.

6.6.1. Connection of cables

Feed cables have to be chosen on the basis of power, distan-
ce, voltage drop and temperature.
For  connection  of  cables  in  the  well,  use  thermo-shrinking
insulation  sheathes  or  other  systems  used  for  submerged
cables.
Before lowering the motor into the well, use appropriate instru-
ments to measure continuity between phases and perform an

isolation  test  between  each  single  phase  and  the  earth  con-
ductor.
The  isolation  test  should  be  repeated  with  motor  and  cable
jonction fully submerged.

6.7. Operation with frequency converter

During starting and/or use, the minimum frequency must not
be lower than 30 Hz, keeping the voltage/frequency ratio con-
stant.

A filter must be inserted between the inverter and the
motor that guarantees the following voltage gradients:
In  motors  with  water  and  glycol  and  standard  wrap-
ping (PVC/HT):

dV/dt≤500 V/μs e Vpp

(1)

≤1400V

In  motors  with  water  and  glycol  and  special  wrapping
(PE2+PA): 

dV/dt≤650 V/μs e Vpp

(1)

≤1800V

(1)

Voltage between one peak and the next generated by the drive.

Conditions  to  be  respected  no  matter  how  long  the  power
cables are.

6.8 Operation with soft-starter

The SOFT-STARTER device must have a voltage ramp, not
a current ramp.
Always  make  sure  that  the  soft-starter  is  excluded  when  the
unit starting phase has ended.

6.9 Setting the PT100 probes

If  there  are  PT100  probes  inside  the  motor,  do  the  following
to set the intervention temperature threshold:
- Start  the  motor  pump  and  position  yourself  at  the  working

point where the highest absorbed power is; the internal tem-
perature will increase progressively and will be monitored by
the probe.  When running correctly (up to 2 hours can pass
according to the motor) the temperature that is read will sta-
bilize.

- When  the  temperature  is  stable,  set  the  first  alarm  at  a

value  equal  to  the  temperature  read  +3°C;  the  alarm  must
register  that  the  temperature  has  been  exceeded  for  regi-
stration of the first inspection.

- The second alarm, which controls motor stopping, has to be

set at a value equal to the temperature read +6° C; restar-
ting (with recording of the temperature that has been excee-
ded)  can  be  automatic  but  must  occur  with  a  delay  of  at
least 15 minutes from stopping, or at an internal motor tem-
perature that is 20° C lower than the set alarm temperature; 

The 2nd alarm, with motor shutdown, cuts in in cases of:
- Overload
- Poor cooling
- Frequent starts 
With the motor wrapped in PVC the maximum set temperatu-
re of the second alarm can be 58°C
With the motor wrapped in PE2+PA the maximum set tempe-
rature of the second alarm can be 75°C.

7 SWITCH OFF OF THE PUMP

The appliance must be switch off every time there are
faults. (see troubleshooting).

The product is designed for a continuous duty,  the switch off
is  performed  by  disconnecting  the  power  supply  by  means
the  expected  disconnecting  devices.  (see  paragraph  "6.6
Electrical connection").

OFF

i

ON

IST CSR 09_16 Rev2_MXS 11_03con gall  07/11/16  08:37  Pagina 8

Содержание CS-R Series

Страница 1: ...L USO Pagina 2 Italiano OPERATING INSTRUCTIONS Page 6 English BETRIEBSANLEITUNG Seite 10 Deutsch INSTRUCTIONS POUR L UTILISATION Page 14 Fran ais INSTRUCCIONES DE USO P gina 18 Espa ol DRIFT INSTALLA...

Страница 2: ...e e indirizzo del Fabbricante Ragione sociale Calpeda S p A Indirizzo Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italia www calpeda it 1 3 Operatori autorizzati Il prodotto rivolto a oper...

Страница 3: ...aordinaria in cui si prevedere di togliere il filtro previsto l uso dei guanti per la protezione delle mani Segnale DPI obbligatori PROTEZIONE DELLE MANI guanti per la protezione da rischio chimico te...

Страница 4: ...proteggere la pompa contro il funzionamento a secco instal lare sonde di livello 6 6 1 Giunzione cavi Scegliere un adeguato cavo di alimentazione in base a potenza distanza caduta di tensione e tempe...

Страница 5: ...di sovrac carico scatta dopo alcuni minuti di fun zionamento 5 Scatta il rel dif ferenziale PROBABILI CAUSE a L interruttore di selezione si trova sulla posizione OFF b Il motore non viene alimentato...

Страница 6: ...facturer name and address Manufacturer name Calpeda S p A Address Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italia www calpeda it 1 3 Authorized operators The product is intended for use...

Страница 7: ...ventions where it is required to remove the filter safety gloves are required Signal individual protection device HAND PROTECTION gloves for protection against chemical thermal and mechanical risks 5...

Страница 8: ...voltage drop and temperature For connection of cables in the well use thermo shrinking insulation sheathes or other systems used for submerged cables Before lowering the motor into the well use approp...

Страница 9: ...inutes of opera tion 5 The differential relay cuts in PROBABLE CAUSE a The selector switch is at OFF b The motor is not being powered c The automatic control devices the level switch etc do not give c...

Страница 10: ...eim eingeschalteten Ger t vorzunehmen sind 1 2 Firmenbezeichnung und Adresse vom Hersteller irmenbezeichnung Calpeda S p A Adresse Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italien www c...

Страница 11: ...mm Obligatorische PSA HANDSCHUTZ Schutzhandschuhe zum Schutz vor chemi schen thermischen und mechanischen Risiken 5 LAGERUNG UND UMSCHLAG Das Produkt ist verpackt damit der Inhalt nicht besch digt wir...

Страница 12: ...dung im Brunnen w rmeverengende Isoloierhu lsen oder andere Systeme fu r Unterwasser Kabel verwenden Vor dem Absenken des Motors in den Brunnen ist mit Instrumenten die Kontinuit tsmessung zwischen de...

Страница 13: ...ieb in Kraft 5 Das Differentialrelais l st sich aus M gliche Ursachen a Der W hlschalter befindet sich in Position OFF b Der Motor wird nicht gespeist c Die automatischen Kontrollvorrichtungen Niveaus...

Страница 14: ...iale Calpeda S p A Adresse Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italie www calpeda it 1 3 Op rateurs autoris s Le produit s adresse des op rateurs experts qui se parta gent entre ut...

Страница 15: ...els sont les dispositifs appropri s au travail r aliser Lors des op rations de maintenance ordinaire et extraordinaire o il faut enlever le filtre l utilisation des gants pour la protection des mains...

Страница 16: ...e d alimentation appropri en fonction de la puissance de la distance de la chute de tension et de la temp rature Pour la jonction des c bles du puits utiliser des gaines ther mor tractables sp ciales...

Страница 17: ...clen che apr s peu de minutes de fonc tionnement 5 Le relais diff ren tiel se d clenche CAUSES PROBABLES a Le sectionneur est en position OFF b Le moteur n est pas aliment c Les dispositifs de contr l...

Страница 18: ...on el dispositivo encendido 1 2 Nombre y direcci n del Fabricante Nombre Calpeda S p A Direcci n Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italia www calpeda it 1 3 Operadores autorizado...

Страница 19: ...ajos descritos En las operaciones de mantenimiento ordinario y extraordinario en que se va a quitar el filtro se prev el uso de guantes para la protecci n de las manos Se ales DPI necesarias PROTECCI...

Страница 20: ...stalar sondas de nivel 6 6 1 Uni n con cables Elija un cable de alimentaci n adecuado seg n la potencia distancia ca da de presi n y temperatura Para la uni n de los cables en el pozo use las vainas t...

Страница 21: ...segundos de funciona miento 4 El rel de sobrecarga se acciona despu s de unos minutos de funciona miento 5 El rel diferen cial se acciona CAUSAS PROBABLES a El interruptor de selecci n est en la posic...

Страница 22: ...gsnamn och tillverkarens adress F retagsnamn Calpeda S p A Adress Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italien www calpeda it 1 3 Auktoriserade operat rer Produkten r avsedd att anv...

Страница 23: ...tt anv nda under installations start och underh llsfaserna Skyddshandskar ska anv ndas under l pande och s rskilt underh ll n r filtret ska avl gsnas M rke Obligatorisk personlig skyddsutrustning SKYD...

Страница 24: ...lama m ste v ljas med h nsyn till effekt l ngd sp nningsfall samt temperatur F r anslutning av kablarna i borrh let skall krympslang eller annan skarvanordning anv ndas avsett f r dr nkbara pum par F...

Страница 25: ...el et utl ses efter ett par minuters funktion 5 Differentialrel et utl ses M JLIGA ORSAKER 1 V ljarbrytaren st r i l ge AV b Motorn f rs rjs inte c De automatiska kontrollanordningarna niv brytare osv...

Страница 26: ...ngrepen die uitgevoerd moeten worden nadat de machine uitgeschakeld en losgekoppeld is van de energiebronnen Ingrepen die uitgevoerd moeten worden terwijl de machine ingeschakeld is 1 2 Handelsnaam en...

Страница 27: ...s met zich mee 4 4 Veiligheids en informatietekens Voor dit type product zijn geen tekens op het product voorzien 4 5 Persoonlijke beschermingsmiddelen PBM In de fasen van installatie inschakeling en...

Страница 28: ...ermingsmechanisme dat het toevoersys teem scheidt in het geval van defecten richting aarde van de elektrische pomp Beveilig de pomp tegen droogdraaien d m v elektrocodes 6 1 1 Bevestiging van de kabel...

Страница 29: ...EN 1 De motor gaat niet aan 2 De zekeringen branden door bij het inschakelen 3 Het overbela stingrelais treedt na enke le seconden functioneren in werking 4 Het overbela stingrelais treedt na enke le...

Страница 30: ...1 5 1 5 Calpeda S p A 1 2 2 CS R 70 30 Dowcal N DowChemical CEE 6 2 2 1 Motor Max Cooling Max Liquid minimum starts P2 temperature flow velocity per hour 6CS R 4 11 kW 30 C 0 1 m s 15 13 15 kW 30 C 0...

Страница 31: ...50 380 44 50 400 42 50 415 42 60 21 3 460 40 2 60 18 5 460 36 1 60 18 5 380 41 3 3 D IP68 S1 IEC 60034 1 Max Thurst Load 30000N Serial Cos No 2015538127 N min 1 0 85 2830 2840 0 82 0 77 2855 0 845 34...

Страница 32: ...t dry running 6 6 1 a 6 7 30 Hz inverter PVC HT dV dt 500 V s Vpp 1 1400V PE2 PA dV dt 650 V s Vpp 1 1800V 1 T drive 6 8 soft starter SOFT STARTER soft starter 6 9 PT100 PT100 2 3 C 6 C 15 20 C 2 PVC...

Страница 33: ...CALPEDA SpA CALPEDA SpA 9 10 10 1 CALPEDA S p A i i OFF 11 OFF 1 2 3 4 5 OFF a b c a b c d e f a b c d d f g a ON a b c a b 5 5 c d e f a 3 d b c 3 b b e f g a IST CSR 09_16 Rev2_MXS 11_03con gall 07...

Страница 34: ...nza Italia www calpeda it 1 3 1 4 1 5 1 5 Calpeda S p A 1 2 2 CS R 70 30 Dowcal N DowChemical CEE 6 2 2 1 P2 6CS R 4 11 kW 30 C 0 1 m s 15 13 15 kW 30 C 0 2 m s 15 18 5 kW 25 C 0 2 m s 15 22 30 kW 25...

Страница 35: ...4 50 400 42 50 415 42 60 21 3 460 40 2 60 18 5 460 36 1 60 18 5 380 41 3 3 D IP68 S1 IEC 60034 1 Max Thurst Load 30000N Serial Cos No 2015538127 N min 1 0 85 2830 2840 0 82 0 77 2855 0 845 3430 0 81 3...

Страница 36: ...4 6 5 6 6 3 5 30 6 6 1 6 7 30 PVC HT dV dt 500 V s Vpp 1 1400V PE2 PA dV dt 650 V s Vpp 1 1800V 1 6 8 6 9 PT100 PT100 2 3 C 6 C 15 20 C 2 58 C PE2 PA 75 C 7 6 6 i OFF ON IST CSR 09_16 Rev2_MXS 11_03co...

Страница 37: ...S p A Calpeda S p A 9 10 10 1 Calpeda S p A i i OFF 11 OFF 1 2 3 4 5 a OFF b c a b c a b c d e f a b c d e f g a a ON b c a b c a b 5 5 c d e f a 3 d b c 3 b d e f g a IST CSR 09_16 Rev2_MXS 11_03con...

Страница 38: ...ntino Vicenza Italia www calpeda it 1 3 1 4 1 5 Calpeda S p A 1 2 2 CS R 70 30 N EEC 6 2 2 1 P2 6CS R 4 11 kW 30 C 0 1 m s 15 13 15 kW 30 C 0 2 m s 15 18 5 kW 25 C 0 2 m s 15 22 30 kW 25 C 0 2 m s 13...

Страница 39: ...400 42 50 415 42 60 21 3 460 40 2 60 18 5 460 36 1 60 18 5 380 41 3 3 D IP68 S1 IEC 60034 1 Max Thurst Load 30000N Serial Cos No 2015538127 N min 1 0 85 2830 2840 0 82 0 77 2855 0 845 3430 0 81 3455 0...

Страница 40: ...6 6 1 6 7 30HZ PVC HT dV dt 500 V s e Vpp 1 1400V PE2 PA dV dt 650 V s e Vpp 1 1800V 1 6 8 6 9 PT100 PT100 3 6 15 20 PVC 58 PE2 PA 75 7 6 6 8 CALPEDA CALPEDA S P A OFF ON i i i IST CSR 09_16 Rev2_MXS...

Страница 41: ...Rev 2 9 10 10 1 CALPEDA S P A OFF 11 OFF 1 2 3 4 5 a OFF b c a b c a b c d e f a b c d e f g a a ON b c a b c a b 5 5 c d e f a 3 d b c 3 b d e f g a IST CSR 09_16 Rev2_MXS 11_03con gall 07 11 16 08 3...

Страница 42: ...83 84 87 87 85 2825 2815 2830 2840 2835 2840 2855 2840 2820 2850 2845 2870 2860 3 3 2 4 1 4 5 2 5 5 5 4 4 5 5 3 5 3 6 5 1 1 5 1 5 2 1 7 2 5 2 6 1 95 2 5 1 7 2 2 2 4 2 30000 30000 30000 30000 30000 300...

Страница 43: ...05 2895 2905 60000 60000 60000 60000 60000 60000 60000 60000 8 NEMA 43 48 CS R Rev 2 12 1 Dimensioni e pesi Dimensions and weights Abmessung und Gewicht Dimensions et poids Dimensiones y pesos M tt oc...

Страница 44: ...44 48 CS R Rev 2 IST CSR 09_16 Rev2_MXS 11_03con gall 07 11 16 08 37 Pagina 44...

Страница 45: ...t Giunzione cavi Connection of cables Kabelverbindung Jonction des c bles Uni n de los cables Anslutning av kablar Bevestiging van de kabels grigio grey grau gris gris gr grijs marrone brown braun mar...

Страница 46: ...46 48 CS R Rev 2 IST CSR 09_16 Rev2_MXS 11_03con gall 07 11 16 08 37 Pagina 46...

Страница 47: ...EG Vorschriften 2006 42 EG 2014 30 EU 2014 35 EU entspre chen DECLARATION OF CONFORMITY KONFORMIT TSERKL RUNG DECLARATION DE CONFORMITE Nous Calpeda S p A d clarons que les moteurs 6CS R 8CS R 10CS R...

Страница 48: ...s p a Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italia Tel 39 0444 476476 Fax 39 0444 476477 E mail info calpeda it www calpeda com IST CSR 09_16 Rev2_MXS 11_03con gall 07 11 16 08 37 Pa...

Отзывы: