5.3. LED display
The SCU assembly has 2 LEDs:
EC ST and RUN:
LED
Colour
Displaye
Meaning
EC ST
Off
Init
Green
Blinking
PRE-OPERATIONAL
Green
Single Flash
SAFE-OPERATIONAL
Green
Off
OPERATIONAL
Red
Off
No errorr
Red
Blinking
Invalid configuration
Red
Single Flash
Ocal error
Red
Double Flash Watchdog Timeout
RUN
-
Off
No power supply voltage
Orange
Blinking
Control is in startup phase or STOP or firmware
update is carried out.
Orange
Pernanently
lit
Local mode of the assembly (without network
connection)
Green
Blinking
Control function correct;
Application runs but is not (yet) validated)
Green
Permanently
lit
Control function correct.
Application runs and is validated.
Red
Blinking
Alarm (application error)
–
the assembly is in the in
a safe operating state. Error status can be reset.
Red
Permanently
lit.
Fatal error
–
the assembly is in the safe operation
mode.
NOTICE
:
For all operating states except RUN the outputs are passivated, i. e. switched off safely. In rhe
RUN state, the state of the outputs is dependent on the implemented PLC programme.
5.4. Parametrization
Parametrisation is carried out via the programme SafePLC
2
.
To be able to send the data to the assembly, a programme adapter is needed. Before use, the
driver of the programme adapter must be installed for the first time.
The description of parametrisation must be taken from the programme manual.
5.5. Regular functional test
To guarantee the safety of the assemblies, once per year a functional test of the safety functons
must be carried out. For the functional test, once a year the blocks used in the parametrisation
(inputs, outputs, monitoring fnctions) and logic modules must be tested with respect to their
functioning, or rather, with respect to their shutoffg getestet werden.