Programming manual SCU-series
HB-37500-820-10-12F-EN SCU Programming manual
Page 153 of 252
Status: 19.03.2021
Startup type
Function
AWL
Plan
Auto
Automatic start after the recet of the
equipment or after the input has
been enabled.
The output of the input element
changes to “1”
when the safety
circuit is closed / active according to
the definition of the switch type.
Manual start (by
hand)
Manual start after the reset of the
equipment. This output of the input
element changes to
“1” when the
the safety circuit is closed / active
according to the definition of this
switch type, and the start button
has been pressed once.
The output changes to “0” after the
safety circuit is open
E1: switch function
E2: start button
M.(X1): auxiliary flag 1
LD E.1
AND E.2
S M.(X1)
LD NOT E.1
R M.(X1)
LD M.(X1)
AND E.1
ST IE.X
Start-Taster
Ausgang
Schaltfunktion
Start
(monitored)t
Manual start after equipment reset
with monitoring of start circuit for
static 1-signal.
The output of the input element
changes to “1” if the safety circuit is
closed according to the switch type,
and the start button has been
pressed and released once. The
output changes to “0”, after the
safety circuit is open.
E1: switch function
E2: start button
M.(X1): auxiliary flag 1
M.(X2): auxiliary flag 2
LD E.1
AND E.2
S M.(X1)
LD NOT E.1
R M.(X1)
LD M.(X1)
AND E.1
AND NOT E.2
S M.(X2)
LD NOT E.1
R M.(X2)
LD M.(X2)
AND E.1
ST IE.X
Start-Taster
Ausgang
Schaltfunktion
Schaltfunktion
Ausgang
Geräte-Anlauf
Switching
function
Start button
Output
Switching
function
Start button
Output
Start equipment
Switching function
Output