Programming manual SCU-series
HB-37500-820-10-12F-EN SCU Programming manual
Page 177 of 252
Status: 19.03.2021
FDB (FSoE Disconnect Block)
Safe disconnection of an FSoE connection
Number:
c. f.
“Overview of safety modules“
Function:
“
Disconnect B
lock“
is used to temporarily disable the FSoE connection- The
detection, which device must be disabled, is set via the FSoE address. By
the function, an error status in the Master in case of defined shut-off / defined
disconnection of a Slave block is avoided.
Input:
FSoE connection active / inactive
RESET function:
no reset necessary
Description of the function:
•
At the activation of Disconnect Block, the FSoE connection of the participant must be
disables, and the process data are disabled (“0“).
•
At the deactivation of the Disconnect Block, the Master block tries to restore the FSoE
connection to the Slave. If the connection has been successfully established, the FSoE
Slave continues to work normally, and the input information / the output information
work with a cyclical update of the input data / the output data. If the FSoE connection is
not established within a determined, configurable time, an alarm is triggered.
NOTICE:
When using SSB, automatically both FSoE connections are disconneted.