Example of an activation:
Example of an input:
The max. travel distance of the material feeding system of a production plant shall be safely
monitored in jog operation. According to the risk analysis this travel distance is no more than 50
mm. A wrong travel distance in the opposite direction shall be monitored.
1. Jog steptt
The relative travel distance (only available in the incremental encoder) is monitored => input of
max. travel distance according to risk analysis with a tolerance = 55 mm
2. Monitoring of the travel distance
Permitted travel distance in opposite direction (=creep movement of the drive) = 1 mm/s
3. Monitoring input
The monitoring has two inputs to indicate the direction. An active direction signal activates the
monitoring function.
After the actication of the monitoring device, the direction must be indicated by an umambiguous
signal => Switches for the direction are directlon are directly connected to the standard inputs of
the SCU => selection I 01, I 02
NOTICE:
If both input signals are “1”, this is
recognised as an impermissible status, and an alarm message
is enabled.
[Achse]: 1