Programming manual SCU-series
HB-37500-820-10-12F-EN SCU Programming manual
Page 76 of 252
Status: 19.03.2021
4.4.3. Selecting the units / network components
After the start of the program SafePLC
2,
first the suitable variant of the SCU-x-EC/x must be
selected from the
“
Library
“
–
by dragging it into the main window (example: SCU-1-EC)
–
tab
“terminal scheme”
.
Via the property window (bottom right), the parameters of the selected units (e. g. cycle time, ID,
etc) can be determined.
Figure 51: selection of Master
For our example, an SCU-1-EC is inserted here, and the following parameters are entered:
Module address:
0
(selectable
–
see plan)
Cycle timeit:
16ms
(from the data sheet)
Local network:
EtherCAT
(EtherCAT to the central computer)
Serial number:
4
(back of units)
After the insert of the FSoE-Master units, automatically the selection folder for Slave units (FSoE
and EtherCAT) is shown (Before the folder is hidden.).
Afterwards, the Slave units for axle monitoring and IOs can be added. In the same window also the
inputs and the outputs of the unit can be selected. Here, no difference is made between FSoE and
EtherCAT.
–
The differenciation is made via parameters.
Slaves the read-in of axle data:
•
SSB...
(Safe Sensor Box
–
reading in of encoder data of 6 encoders BBH)
•
SDU…
(Safe Drive Unit
–
reading in of encoder data of one encoder BBH)
•
AX...
(
–
evaluate encoder data of one encoder)
•
Incremental Encoder Electronic GmbH (
–
read in encoder data of one encoder)
•
SDC
(
–
read in external encoder data (option encoder) LT-i)
Property