Programming manual SCU-series
HB-37500-820-10-12F-EN SCU Programming manual
Page 245 of 252
Status: 19.03.2021
0xAnn0
1
Connection state
1
2
ENUM[16]
R
100 = Reset
101 = Session
102 = Connection
103 = Parameter
104 = Data
105 = Failsafe
2
Connection
diagnosis
1
2
UNSIGNED
16
R
Diagnosis bits of FSoE Connection
Bit0..3:
0 = no error
1 = wrong command
2 = unknown command
3 = wrong connection ID
4 = wrong CRC
5 = watchdog expired
6 = wrong FSoE address
7 = wrong data
8 = wrong communication parameter length
9 = wrong communication parameter
10 = wrong application parameter length
11 = wrong application parameter
12 = unexpected session command
13 = if failsafe data are communication error:
failsafe data received
Bit 4:
0 = error in FSoE Master
1 = error in FSoE Slave
Bit 5:
1 = FSoE slave sends no process data
Bit 6:
1 = connection in startup
Bit 7:
1 = FSoE Master sends no process data (FSoE
Master in failsafe)