50
P/N 133487
Banner Engineering Corp.
•
Minneapolis, U .S .A .
www .bannerengineering .com • Tel: 763 .544 .3164
SC22-3 Safety Controller
Instruction Manual
Configuration — Onboard Interface
5.4.3 Outputs/System Settings
Safety Outputs
This option is used to configure the safety outputs . Use the up/
down arrows to select Safety Outputs and press OK . Select the
output to configure in the resulting menu and press OK . You will
be given the opportunity to change the output’s name, and give it
an ON- or OFF-delay .
Status Outputs
This option is used to configure the status outputs . Status
outputs are configured individually . Use the up/down arrows to
select Status Outputs and press OK .
• Use the left/right arrows to select the status output to
configure (O1 to O10), and press OK .
• The Status Output Properties menu appears . This menu is
used to configure the status output to indicate:
— The status of an input device
— The status of a safety output
— A system lockout
— An I/O fault
— The need to perform a system reset
— The need to perform a reset operation on a safety output
— When an input is being muted
Name the Status Output — Use the up/down arrows to select
Change Name and press OK .
• Use the left/right arrows to select the character to be
changed (up to 10 characters) .
• Use the up/down arrows to change the character (choices
A-Z, 0-9, -, +, or space) .
• Press OK when done .
• When the display returns to the Status Output Properties
menu, the top line of the display will display the new name .
Select the function of the status output — Options are:
unassigned (no function), track input, track output, track fault
status, waiting for reset, and mute status . Use the up/down
arrows to select Select Function and press OK .
• Use the left/right arrows to select a function, then press OK .
• The display returns to the Status Output Properties menu .
Select the source for the status output function — Select
Select Source and press OK .
• Use the left/right arrows to select a device and press OK .
• The display returns to the Status Output Properties menu .
Select the signal convention — The options are:
24V = Input Active and 24V = Input Inactive (e .g ., if tracking
an input; see Section 3 .7 for more information) .
• Use the left/right arrows to toggle between the selections
and press OK .
To save the settings for this output, select <Done> and press
OK . The display returns to the Outputs/System Settings menu .
To configure additional status outputs, select Status Outputs,
select another status output and repeat the steps above .
When the last status output is configured, press ESC to return
to the Edit Configuration menu .
System Settings
Select the output’s reset mode, power up mode and whether
mute will be active on power-up .
System Reset — Use the left/right arrows to toggle between
Monitored or Non-Monitored, and press OK .
Power Up Option — Use the left/right arrows to select among
Normal, Auto, or Manual, and press OK .
Mute on Power-Up — Use the left/right arrows to toggle
between Off or On, and press OK .
System
Settings
Terminal
Assignments
Input/Output
Mapping
Status Output
Settings
Status
Outputs
Safety
Outputs
Edit
Configuration
(Section 5.4)
Edit
Input
Delete
Input
Inputs
(Section 5.4.2)
Outputs/System
Settings
(Section 5.4.3)
Configuration
Summary
(Section 5.4.4)
←
O
K
ES
C
→
←
O
K
ES
C
→
←
O
K
ES
C
→
←
O
K
ES
C
→
←
O
K
ES
C
→
Add Input
(Section 5.5)
Save
Configuration
(Section 5.4.5)
Name
Configuration
(Section 5.4.1)
Edit Configuration continued