118
P/N 133487
Banner Engineering Corp.
•
Minneapolis, U .S .A .
www .bannerengineering .com • Tel: 763 .544 .3164
SC22-3 Safety Controller
Instruction Manual
Appendix C
Edit Inputs menu
ESC→
Edit Configuration menu
Configure the Status Outputs
To configure the status outputs, select Outputs/System
Settings and press OK .
Select Status Outputs and press OK .
Use the left/right arrow keys to select the status output to
configure . In this case, select Status Output 01 and press OK .
The next menu displayed is the Status Output Properties
menu . From this menu you can configure the status output(s) .
Configure:
• Status output 01 to track the state of ES01
• Status output 02 to signal when a reset operation is needed
for Safety Output SO1
Configure Status Output 01
Change the name of 01 by selecting Change Name and
pressing OK .
Use the left/right arrow keys to select the character to be
changed (up to 10 characters) .
Use the up/down arrow keys to change the character (choices
A-Z, 0-9, -, +, or space) .
Set the name to ES01 and press OK .
The display returns to the Status Output Properties menu . The
top line of the display now displays the name assigned to the
status output .
Configure the status output to track an input . Select Select
Function and press OK .
Using the left/right arrow keys, select Track Input and press OK .
The display returns to the Status Output Properties menu .
Configure the status output to track the E-stop input, ES01 .
Select Select Source and press OK .
Using the left/right arrow keys, select ES01 and press OK .
The display returns to the Status Output Properties menu .
Status output 01 is now configured . To save the settings, select
<Done> and press OK .
The display returns to Outputs/System Settings menu .
To configure additional Status Outputs, select Status Outputs,
select the status output to configure and repeat the steps that
were performed for status output 01 .