SC22-3 Safety Controller
Instruction Manual
Appendix A
A.10.2 SC22-3 Bypass Switch Hookup Options
The device(s) is shown not actuated or in the Off state .
Dual-Channel (2 terminals or 3 terminals): This circuit
typically can meet ISO 13849-1 category 2 or category 3
requirements depending on the safety rating and installation of
the bypass switch(es) . Dual-channel 3-terminal hookup uses
pulse monitoring and can detect a short circuit to another source
of power . Both 2- and 3-terminal hookup can detect a short
between channels when the contacts are open if the short is
present longer than 2 seconds .
Bypass Switches - Dual Channel
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Bypass Switches - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
20-Sept-06 Rev. D - Moved 24V, ON and OFF text closer to drawings.
21-Nov-06 Rev E - Added + sign to 2-Ch, 3 Terminals; 2-Ch, 4 Terminals; 2x Complementary, 4 Terminals
10-Jan-07 Rev F - C sign text to outlines
25-May-07 Rev G - Changed all PNP drawings and 2x Complementary, 5 Terminals (moved + sign)
OFF
OFF
Bypass Switches - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ON
OFF
2x Complementary,
4 Terminals, 2 PNP
ON
OFF
ON
OFF
Bypass Switches - Dual Channel
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Bypass Switches - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
20-Sept-06 Rev. D - Moved 24V, ON and OFF text closer to drawings.
21-Nov-06 Rev E - Added + sign to 2-Ch, 3 Terminals; 2-Ch, 4 Terminals; 2x Complementary, 4 Terminals
10-Jan-07 Rev F - C sign text to outlines
25-May-07 Rev G - Changed all PNP drawings and 2x Complementary, 5 Terminals (moved + sign)
OFF
OFF
Bypass Switches - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ON
OFF
2x Complementary,
4 Terminals, 2 PNP
ON
OFF
ON
OFF
Dual-Channel (PNP device): This circuit can meet ISO 13849-1
category 2, 3, or 4 requirements depending on the safety rating,
installation, and the fault detection (e .g ., short circuit) capabilities
of the bypass switch(es) . The SC22-3 does not provide short
circuit detection in this configuration .
Bypass Switches - Dual Channel
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Bypass Switches - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
20-Sept-06 Rev. D - Moved 24V, ON and OFF text closer to drawings.
21-Nov-06 Rev E - Added + sign to 2-Ch, 3 Terminals; 2-Ch, 4 Terminals; 2x Complementary, 4 Terminals
10-Jan-07 Rev F - C sign text to outlines
25-May-07 Rev G - Changed all PNP drawings and 2x Complementary, 5 Terminals (moved + sign)
OFF
OFF
Bypass Switches - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ON
OFF
2x Complementary,
4 Terminals, 2 PNP
ON
OFF
ON
OFF
Dual-Channel (4 terminals): This circuit can meet ISO 13849-1
Category 2, 3, or 4 requirements depending on the safety rating
and the installation of the bypass switch(es) . This circuit can
detect a short circuit between channels or to another source of
power .
Optical Sensors and Protective Stop - Dual Channel
Optical Sensors and Protective Stop - Single Channel
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Muting Sensor Pair - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary PNP
24V
01-Aug-2007 Optical Sensors and Protective Stop Circuit drawings are the same
OFF
OFF
ON
OFF
24V
1-Ch.
1 Terminal
1-Ch.
2 Terminals
1-Ch.
1 Term, PNP
Revision History
Complementary (2 terminals or 3 terminals): This circuit can
meet ISO 13849-1 category 2, 3, or 4 requirements depending
on the safety rating and the installation of the bypass switch(es) .
This circuit can detect a short circuit between channels . In the
actuated condition (e .g ., S1 open/S2 closed, as shown below)
a short across the closed contact can cause the response
time to increase based on the debounce time . In this situation,
the response time could be longer as specified, based on the
(selected) debounce time, see Section 3 .2 .2 .
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFF
OFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ON
OFF
2x Complementary,
4 Terminals, 2 PNP
ON
OFF
ON
OFF
S1 S2
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFF
OFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ON
OFF
2x Complementary,
4 Terminals, 2 PNP
ON
OFF
ON
OFF
S1 S2
Complementary (PNP device): This circuit can meet ISO
13849-1 category 2, 3, or 4 requirements depending on the
safety rating and the installation of the bypass switch(es) .
This circuit can detect a shortcircuit between channels . In the
actuated condition (e .g ., S1 OFF/S2 ON, as shown below) a
short across the closed contact can cause the response time
to increase based on the debounce time . In this situation, the
response time could be longer than specified, based on the
(selected) debounce time, see Section 3 .2 .2 .
Two-Hand Operation
2-Ch, 2 Terminals
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
2-Ch, 2 Terminals
2 PNP
Two Hand Operation - 2x Dual Channel Complementary
2x Complementary,
4 Terminals
2x Complementary,
5 Terminals
2x Complementary,
4 Terminals, 4 PNP
Revision History
Rev C - Corrected “OFF” and “ON” on Two-hand Operation - 2x Dual Channel Complementary, 2x Complementary, 4 Terminals, 4 PNP
20-Sept-06 Rev. D - Moved 24V, ON and OFF text closer to drawings.
13-Oct-06 Rev. E Gray lines moved below the black lines
21-Nov-06 Rev. F - Added + sign to 2-Ch, 3 Terminals, 2-Ch, 4 Terminals, 2x Dual Channel Complementary, 5 Terminals
10-Jan-07 Rev. G - C sign text to outlines, changed gray lines to 6 pt. dashed lines
25-May-07 Rev H - Changed 2-Ch, 2 Terminals 2 PNP; 2x Complementary, 5 Terminals (centered arrow) and 2x Complementary, 4 Terminals, 4 PNP
20-Sept-07 Rev I - Added another 2-ch, 2 Terminal for the manual
24V
24V
OFF
OFF
ON
OFF
ON
OFF
24V
S1 S2
2x Complementary (4 terminals or 5 terminals): This circuit
can meet ISO 13849-1 category 4 requirements depending on
the design and installation of the bypass switch(es) . This circuit
can detect a short circuit between channels . In the guard closed
condition (e .g ., S1 open/S2 closed) a short across the closed
contact can cause the response time to increase based on the
debounce time . In this situation, the response time could be
longer than specified, based on the (selected) debounce time,
see Section 3 .2 .2 .
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFF
OFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ON
OFF
2x Complementary,
4 Terminals, 2 PNP
ON
OFF
ON
OFF
S1 S2
Bypass Switches - Dual Channel
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Bypass Switches - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
20-Sept-06 Rev. D - Moved 24V, ON and OFF text closer to drawings.
21-Nov-06 Rev E - Added + sign to 2-Ch, 3 Terminals; 2-Ch, 4 Terminals; 2x Complementary, 4 Terminals
10-Jan-07 Rev F - C sign text to outlines
25-May-07 Rev G - Changed all PNP drawings and 2x Complementary, 5 Terminals (moved + sign)
OFF
OFF
Bypass Switches - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ON
OFF
2x Complementary,
4 Terminals, 2 PNP
ON
OFF
ON
OFF
S1 S2
2x Complementary (PNP device): This circuit can meet ISO
13849-1 category 4 requirements depending on the design and
installation of the bypass switch(es) . This circuit can detect a
short circuit between channels . In the actuated condition (e .g .,
S1 OFF/S2 ON) a short across the closed contact can cause
the response time to increase based on the debounce time . In
this situation, the response time could be longer than specified,
based on the (selected) debounce time, see Section 3 .2 .2 .
Enabling Device Circuit Diagrams - Dual Channel
2-Ch, 2 Terminals
2-Ch, 3 Terminals
2-Ch, 4 Terminals
24V
2-Ch, 2 Terminals
2 PNP
Enabling Device Circuit Diagrams - 2x Dual Complementary
2x Complementary,
4 Terminals
24V
2x Complementary,
5 Terminals
Revision History
OFF
OFF
Enabling Device Circuit Diagrams - Dual Complementary
Complementary,
2 Terminals
Complementary,
3 Terminals
Complementary,
2 Terminals, 2 PNP
24V
ON
OFF
2x Complementary,
4 Terminals, 2 PNP
ON
OFF
ON
OFF
S1 S2