SC22-3 Safety Controller
Instruction Manual
Appendix C
Use the left/right arrow keys to select the terminal assignment to
be changed .
Use the up/down arrow keys to change the terminal
assignments .
Set the terminal assignments to S1, S2, S3, and S4, and press
OK .
After the terminal assignments are edited, the display returns to
the Input Properties menu .
Map Outputs
Choose which of the safety output(s) the input will control . Select
Map Outputs in the Input Properties menu and press OK .
To map the input to an output, select the output using the
up/down arrow keys and press OK . A filled-in circle next to an
output indicates the input is mapped to that output . To remove
the input mapping, select the output and press OK . An open
circle indicates the input is not mapped to that output .
Map the E-stop to all three safety outputs, select Save and press
OK .
After mapping the input to the safety outputs, the display returns
to the Input Properties menu .
Set Reset Logic
To set the reset logic, select Reset Logic and press OK .
Use the left/right arrow keys to select the Set Reset Logic
parameter . Select Manual and press OK .
After the Reset Logic parameter is set, the display returns to the
Input Properties menu .
Saving the Input Device Parameters
All of the E-Stop’s parameters have been set . To save the
parameters, select < Done > and press OK .
The display now indicates the input parameters were saved .
Press OK to continue .
The display returns to the Inputs menu .