SC22-3 Safety Controller
Instruction Manual
Appendix B
Add a Mute Sensor Pair
• Click on Add Safety Input .
• Double-click the Mute Sensor icon .
• Create a Mute Sensor configuration with the properties listed
below .
Name: M1+M2
Circuit: Dual-Channel, 4 Terminal
Terminals: S13, S14, S15, and S16
(Use the drop-down terminal number fields to
change the terminal assignment, if needed .)
Map to: OS01
Time limit: 1 minute, 0 second
• Click OK .
NOTE: Mute sensors are mapped to the safety input devices that
they mute and not to the safety outputs .
Add an External Device Monitoring Input
• Click on Add Safety Input .
• Double-click the External Device Monitoring icon .
• Create an External Device Monitoring configuration with the
properties listed below .
Name: EDM01
Circuit: Single Channel, 1 terminal
Reset: Automatic
Terminals: S17 (Use the drop-down terminal number field to
change the terminal assignment, if needed .)
Map to: SO1
• Click OK .
Add More External Device Monitoring Inputs
Add two more External Device Monitoring inputs, one for each
safety output .
• Name them EDM02 and EDM03 .
• Use Single-Channel, 1-terminal circuit types for each .
• Assign terminal S18 to EDM02 and terminal S19 to EDM03 .
• Map EDM02 to SO2 and EDM03 to SO3 .