Chapter 4
CGCM-DLR Unit Configuration
•
Volts per Hertz Lower Slope - Establishes the rate at which the V/Hz
characteristic reduces the generator voltage as a function of generator
frequency below the Lower Knee Frequency setting. Tag
VperHz_LoSlope
in the configuration table stores this value, expressed as
a number that reflects per unit change in voltage for each per unit change
in frequency.
•
The Validate and graph button becomes active when a parameter has been
changed. When clicked, the V/Hz curve established by the knee and slope
values is plotted in the Volts/Hz tab.
Related Parameters:
•
GenRated_V
•
GenRatedFreq
OEL Page
The OEL page is used to configure the unit settings that are related to operation
of the Over-excitation Limiting (OEL) function. The values that are entered on
this page establish the thresholds and time delays that determine the behavior of
the over-excitation limiting function. See the generator manufacturer data sheets
for information such as, exciter full-load and forcing current for setting both
online and offline conditions.
See
for more information on the operation of the OEL function.
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......