232
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Appendix E
Detailed CGCM-DLR Unit Tag Descriptions
Generator Overvoltage Outputs from CGCM Unit
•
Ovr_V_Flt
– This tag is used to communicate the occurrence of an
overvoltage Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
Inputs to CGCM-DLR Unit
•
Undr_V_FltOutEn -
When this tag is a 1 in the configuration, and an
undervoltage Fault occurs (as defined by the Undr_V_Setpt tag), the Fault
Relay is energized. When this tag is a 0 in the configuration, an
undervoltage Condition has no effect on the Fault Relay.
•
Undr_V_Setpt -
This tag configures the generator undervoltage setpoint
that the CGCM-DLR unit uses to recognize an undervoltage condition.
When the condition occurs, the CGCM-DLR unit starts timing toward a
trip.
•
Undr_V_TimeDly -
This setting establishes the time to trip the unit once
the generator Undervoltage setpoint has been exceeded.
•
EngineIdle –
Setting this tag to 1 enables Soft Start mode and disables the
under-frequency, undervoltage, and Loss of PMG protections until the
generator is at rated speed.
Generator Undervoltage Outputs from CGCM Unit
•
Undr_V_Flt -
This tag is used to communicate the occurrence of an
Undervoltage Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
Loss of Sensing Inputs to CGCM-DLR Unit
•
LossSensingFltOutEn -
When this tag is a 1 in the configuration, and a
Loss of Sensing Fault occurs the Fault Relay is energized. When this tag is a
0 in the configuration, a Loss of Sensing Condition has no effect on the
Fault Relay.
Loss of Sensing Outputs from CGCM Unit
•
LossSensingFlt
- This tag is used to communicate the occurrence of a Loss
of Sensing Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......