Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
19
Installation
Chapter
2
Excitation Power
Excitation power is wired to the PMG terminals, whether connected to the
generator output (Shunt Excited) or to a PMG. Connect shunt excited inputs
with a voltage transformer (VT).
PMG inputs are on TB1 and are labeled PMG A, PMG B, and PMG C, to
illustrate their respective phase relationships. Single-phase excitation power must
be connected to terminals PMG A and PMG C. Twisted, shielded cabling is
required for the PMG inputs.
See these wiring diagrams for more information.
Figure 2 - Excitation Power Connections, 3-phase PMG
Figure 3 - Excitation Power Connections, Single-phase PMG
Figure 4 - Excitation Power Connections, Single-phase Shunt
TB1
PM G A
PMG B
PMG C
SHL D 1
SHL D 1
PMG
TB1
PMG A
PMG B
PM G C
SHLD 1
SHLD 1
PMG
TB1
PMG A
PMG B
PM G C
SHLD 1
SHLD 1
Fuse
G
A
C
B
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......