Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
85
CGCM-DLR Unit Configuration
Chapter
4
12.
Open the Module Properties of the CGCM-DLR unit.
13.
In the General tab of Module Properties, update the IP address field to
match the IP address that is configured in
14.
Then, click Apply.
In this example, the IP address was updated from 192.168.1.114 to
10.90.172.72.
15.
In the Connection tab, uncheck the Inhibit Module checkbox and click
Apply.