Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
161
CGCM-DLR Unit Software Interface
Chapter 6
152
4
Real
N/A
VperHz_HiSlope
Volts per Hz Upper Slope
PUV
/PUHz
0…3
38.
156
4
Real
N/A
VperHz_LoKneeFreq
Volts per Hz Low Knee Frequency
Hz
15…90
39.
160
4
Real
N/A
VperHz_LoSlope
Volts per Hz Low Slope
PUV
/PUHz
0…3
40.
164
4
Real
N/A
V_DroopSetpt
Voltage Droop Setpoint
%
-30…30
41.
168
2
INT
N/A
OvrExcV_Setpt
Over-excitation Voltage Setpoint
Volts
/100
100…20,000
42.
170
2
INT
N/A
OvrExcV_TimeDly
Over-excitation Voltage Time
Delay
s/100
10…3000
43.
172
2
INT
N/A
Ovr_V_Setpt
Overvoltage Setpoint
%/100
10000…14000
44.
174
2
INT
N/A
Ovr_V_TimeDly
Overvoltage Time Delay
s/100
10…30,000
45.
176
2
INT
N/A
Undr_V_Setpt
Undervoltage Setpoint
%/100
6000…10,000
46.
178
2
INT
N/A
Undr_V_TimeDly
Undervoltage Time Delay
s/100
10…30,000
47.
180
2
INT
N/A
OpenDiodeMonitorLevel
Open Diode Monitor Level
%/100
0…10,000
48.
182
2
INT
N/A
ShortedDiodeMonitorLev el
Shorted Diode Monitor Level
%/100
0…10,000
49.
184
2
INT
N/A
DiodeMonitorTimeDly
Diode Monitor Time Delay
s/100
10…30,000
50.
186
2
INT
N/A
MainPole
Main Pole
Poles
2…24
51.
188
2
INT
N/A
ExciterPole
Exciter Pole
Poles
2…24
52.
190
2
INT
N/A
Rev_kW_Setpt
Reverse kW Setpoint
%/100
100…10,000
53.
192
2
INT
N/A
Rev_kW_TimeDly
Reverse kW Time Delay
s/100
10…30,000
54.
194
2
INT
N/A
Rev_kVAR_Setpt
Reverse kVAR Setpoint
%/100
100…10,000
55.
196
2
INT
N/A
Rev_kVAR_TimeDly
Reverse kVAR Time Delay
s/100
10…3000
56.
198
2
INT
N/A
OvrFreqSetpt
Over-frequency Setpoint
Hz/100
3000…7000
57.
200
2
INT
N/A
OvrFreqTimeDly
Over-frequency Delay
s/100
10…30,000
58.
202
2
INT
N/A
UndrFreqSetpt
Under-frequency Setpoint
Hz/100
3000…7000
59.
204
2
INT
N/A
UndrFreqTimeDly
Under-frequency Delay
s/100
10…30,000
60.
206
2
INT
N/A
Ovr_I_Setpt
Over-current Setpoint
%/100
1000…32,000
61.
208
2
INT
N/A
Ovr_I_TimeDly
Over-current Time Delay
Time dial
setting
/100
0…990
62.
210
2
INT
N/A
Ovr_I_Curve
Over-current Curve
-
1…17
63.
212
2
INT
N/A
Ovr_I_VrestSetpt
Over-current Voltage Restraint
Setpoint
%/100
0…20,000
64.
214
2
INT
N/A
Spare13
-
-
65.
216
2
INT
N/A
LossExc_I_Setpt
Loss Excitation Current Setpoint
A/100
10…1500
66.
218
2
INT
N/A
LossExc_I_TimeDly
Loss Excitation Current Delay
s/100
10…990
67.
220
4
Real
N/A
UEL_Curve_W_Pt1
Under-excitation Limiting Curve
Power Point 1
W
0…1E+09
68.
224
4
Real
N/A
UEL_Curve_W_Pt2
Under-excitation Limiting Curve
Power Point 2
W
0…1E+09
69.
228
4
Real
N/A
UEL_Curve_W_Pt3
Under-excitation Limiting Curve
Power Point 3
W
0…1E+09
70.
Table 18 - Unscheduled Configuration Read/Write Data Table, Assembly Instance 4
Byte
Size in
Bytes
Type
Bits
Tag Name
Description
Units
Range
Error Code
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......