CGCM-DLR Unit Configuration
Introduction
This section provides a generic set-up and verification procedure for power
generation systems by using the CGCM-DLR unit and the Logix Designer
application. The various configuration parameters that are required to customize
the device to a specific application are presented. Because every application is
unique, read this section carefully and make sure that the configuration entries are
appropriate for the system being implemented.
For additional information on the Studio 5000® environment, see Logix5000™
Controllers Common Procedures, publication
.
Overview of the
Configuration Process
Follow these steps when you use the Logix Designer application to configure the
CGCM-DLR unit.
1.
Gather the necessary equipment and information.
2.
Create a module.
3.
Enter configuration for the module.
4.
Edit configuration for a module when changes are needed.
Preparation
You can record your configuration settings in the table in
. We
suggested that you make a copy of
, use it to record the setup for each
unit, and retain these records for future reference.
The following generator information is used to configure the CGCM-DLR unit:
•
Rated frequency
•
Rated voltage
•
Rated current
•
Rated real power
•
PMG rated voltage
•
Full-load exciter field voltage
•
No-load exciter field voltage
•
Full-load exciter field current
•
Generator direct-access transient time constant T’
do
•
Generator exciter field time constant T
e
•
Number of main and exciter field poles
•
Generator capability curve
•
Generator decrement curve
Consult with the generator manufacturer to be sure that you have the correct
data.
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......