Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
199
CGCM-DLR Unit Math Models
Appendix
B
VAR/Power Factor
Controller
The VAR/PF controller is a summing point type controller and creates the
outside loop of a two-loop system. This controller is implemented as a slow PI
type controller. The voltage regulator forms the inner loop and is implemented as
a fast PID controller.
The model of the CGCM-DLR VAR and power factor controller is shown in
Per-unit Block Diagram for VAR Controller
, respectively. Non-windup limit (V
CLMT
) is used for bounding the
VAR/PF controller output voltages (V
Q
and V
PF
).
Figure 61 - Per-unit Block Diagram for VAR Controller
Figure 62 - Per-unit Block Diagram for PF Controller
Limiters
Both the over-excitation limiter (OEL) and the under-excitation limiter (UEL)
in this implementation are of the summed limiter type as opposed to takeover
type.
Per-unit Block Diagram for Under-excitation Limiter
shows the model of the
under-excitation limiter. The UEL creates the outer loop and the voltage
regulator creates the inner loop. The UEL uses a PI type controller.
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......