Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
47
CGCM-DLR Unit Operation
Chapter
3
Operational Functions
The following sections describe the operational functions of the CGCM-DLR
unit. The functions include the following:
•
•
•
•
•
•
•
•
Excitation Control Modes
The CGCM-DLR unit controls the DC excitation current of the generator
exciter that is based on a number of factors, including the following:
•
The selected control mode
•
The configuration of the CGCM-DLR unit including gains
•
Measured generator voltage and current
•
The applicable setpoint or setpoints
•
The value of the Auxiliary Input
•
Various limiting functions
The CGCM-DLR unit offers several modes of regulation that are selected and
activated by using the software interface to the host Logix programmable
controller. An active EtherNet/IP Data connection must exist with the host
Logix controller for any regulation mode to be active.
The CGCM-DLR unit automatically shuts down excitation if one of these faults
occurs:
•
Overexcitation voltage
•
Reverse VAR
•
Logix controller fault
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......