Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 2
Installation
Figure 13 - Voltage and Current Connection for Three-wire Wye Bus and Four-wire
Wye Generator System with Grounded Neutral
L 1
L2 L3
CB
N
Fuse
Fuse
Fuse
Fuse
Fuse
Fuse
G
A
C
B
TB 3
I1 ( +) 5 A
I1 ( -)
ID ( +) 5 A
I3 ( +) 5 A
I2 ( +) 5 A
I2 ( -)
I3 ( -)
ID (-)
I1 ( +) 1 A
I2 ( +) 1 A
I3 ( +) 1 A
ID ( +) 1 A
TB 6
VBus A
VBus B
VBus C
VBus N
TB5
VGen A
VGen B
VGen C
VGen N
Customer Supplied CT
Shorting Switch or Test
Block
Cross-current CT input
not required for parallel
droop operation.
To optional cross-current
reactive compensation loop.