Specifications
Appendix
D
Loss of PMG
Reverse VAR
Over/Under-frequency
Reverse Power
Rotating Diode Monitor - Range
Attribute
Value
Pickup
< 10V AC single-phase,
< 50V AC 3-phase or an imbalance
greater than 20%
Response time
< 400 ms
Attribute
Range
Increment
Accuracy
Time delay
0.10…300 s
0.10 s
±0.1 s
Attribute
Range
Increment
Accuracy
Pickup
30…70 Hz
0.01 Hz
±2% Hz
Time delay
0.10…300 s
0.10 s
±0.1 s
Attribute
Range
Increment
Accuracy
Pickup
1…100% of rated
generator VA
1%
±0.5% rated VA
Time delay
0.10…300 s
0.10 s
±0.1 s
Attribute
Value
Number of generator poles
0…24
Number of brushless exciter poles
0…24
Increment
2
Fault time delay (applies to both open and
shorted diode conditions)
0.1…300 s
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......