Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
241
Detailed CGCM-DLR Unit Tag Descriptions
Appendix
E
•
kVAR_LS_InputV
-
The product of the RMS magnitude of the reactive
portion of the differential current flowing in the input CT and the
generator terminal voltage is computed. The product is divided by the
rated kVA to determine the reported value for this tag.
•
kVAR_PU_Load
- This tag reports the total p.u. kVAR produced by the
active phases of the generator. The base for this calculation is the
configured generator kVA.
•
kVAR_AnalogPU_Load
– This tag reports the difference between the
KVAR_PU_Load and the kVAR_LS_inputV.