170
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 7
Troubleshooting
Table 27 - Limiting Modes - OEL
Symptom
Most Likely Cause
Diagnostic Action
Corrective Action
Excitation Current exceeds the
programmed OEL limit (OEL does not
limit/activate)
OEL not enabled
Check tag
OEL_En
and configuration
Correct logic or configuration
as required
OEL Gain misadjusted
Force into OEL
Adjust gains as required
OEL not configured
Check OEL settings against generator
excitation requirements / limits
Correct as required
Metering error
See
troubleshooting
troubleshooting
Excitation is unstable when OEL is
active
OEL Gain misadjusted
Force into OEL
Adjust gains as required
Table 28 - Real Power Load Sharing
Symptom
Most Likely Cause
Diagnostic Action
Corrective Action
Units do not share load
Load share lines not properly
connected
Measure voltage at each LS+/-
terminal. Verify that voltage is
PU load
Reconnect LS lines
Open LS terminals; apply a load,
measure LS voltage.
Voltage equals (kW/Rated
kW)*LSFSVoltage
If Voltage is not correct, replace
CGCM-DLR unit after you verify
configuration settings
Load sharing not enabled
Check output tag kW_LS_EN is
set and input tag
kW_LS_ACTIVE is true
If Loadsharing must be disabled no
anomaly is present, otherwise correct
loadsharing logic for tag kW_LS_En
CGCM-DLR unit is not properly
configured
Check configuration parameters
are properly set. See
Input correct configuration
parameters
Wiring errors cause CGCM-DLR unit
to not meter kW properly
Check kW indication from
CGCM-DLR unit against second
meter for accurate kW indication
Correct wiring errors
Governor does not respond to load
share error
Observe that load share error is
being received from CGCM-DLR
unit in host controller
Correct anomaly in Host controller if a
valid load share error is received
Units do not share load equally: one
unit increases the other unit
decreases
Load share lines are connected with
polarity reversed
Observe that load share error is
being received from CGCM-DLR
unit in host controller and error
polarity is correct
Correct polarity on LS lines
Units do not share load equally: units
both change together
Load share full-scale voltage
configurations do not match
Check full load voltage
configuration in each load share
device
Set full load voltage same in all load
share devices
Governor error
Check governor for use of LS
error from CGCM-DLR unit
Correct governor
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......