32
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 2
Installation
Figure 17 - Current Connections for 3-phase Delta Generator with Two CTs
The connections that are shown in this diagram can be used if only two CTs are
available in the generator circuit. Two CTs can be used only with a three-wire
delta generator. The circuit that is shown in this diagram can be substituted for
the CT connections that are shown in Figures
, and
.
Auxiliary Input
The auxiliary input is a +/- 10V DC input. The auxiliary input terminals are on
TB7 and are labeled VREF(+) and VREF(-). SHLD3 is provided for landing the
cable shield. Twisted, shielded cabling is required for the VREF connections.
Remote Excitation Enable Input
The remote excitation enable input is a 24V DC input. The remote excitation
enable input terminals are on TB7 and are labeled EX-D(+) and EX-D(-).
Discrete Outputs
There are two types of discrete outputs: Fault relay outputs and redundancy relay
outputs.
G
TB 3
I1 (+) 5 A
I1 ( -)
I3 (+) 5 A
I2 (+) 5 A
I2 ( -)
I3 ( -)
I1 (+) 1 A
I2 (+) 1 A
I3 (+) 1 A
A
C
B
Customer
S
upplied CT
S
horting
S
witch or Test
Block
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......