212
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Appendix D
Specifications
Remote Excitation Enable Input
Open Collector Outputs (fault relay and redundancy relay)
Field Output
Attribute
Value
Voltage rating
24V DC nom
Input impedance
5.6K
Ω
Logical high voltage, min
18V DC
Logical low voltage, max
5V DC
Attribute
Value
Voltage rating
24V DC nom
Voltage range
18…30V DC
Rated current, max
500 mA
Attribute
Value
Continuous voltage
32, 63, 125V DC
(1)
(1) Available output voltage is dependent on magnitude of excitation power input voltage.
Continuous current
15 A DC
10-second forcing voltage
50, 100, or 200V DC
10 second forcing current
30 A DC
Field resistance, min
32V DC
63V DC
125V DC
2.13
Ω
4.2
Ω
8.3
Ω
Содержание 1407-CGCM-DLR
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM DLR User Manual OriginalInstructions...
Страница 14: ...14 Rockwell Automation Publication 1407 UM002B EN P February 2019 Chapter 1 General Information Notes...
Страница 204: ...204 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix B CGCM DLR Unit Math Models Notes...
Страница 220: ...220 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix D Specifications Notes...
Страница 260: ...260 Rockwell Automation Publication 1407 UM002B EN P February 2019 Appendix G Installing the Add on Profile Notes...
Страница 266: ...266 Rockwell Automation Publication 1407 UM002B EN P February 2019 Index Notes...
Страница 267: ......